What the cold does to a heat pump here
Winter here is the whole question. Heat runs ten months a year, September through June, and the overnight low averages 15°F across December, January and February. That number matters because a standard heat pump has two marks against it, and 15°F is past both. Below 40°F its heat output falls short of what it's rated for. Below about 35°F it often needs backup heat to make up the difference. The average winter night here is below both marks.
This isn't a handful of cold snaps. About 185 nights a year here fall to freezing or below, over half of the roughly 305 nights heat runs at all. On every one of those nights a standard heat pump is working below the point where it puts out its full rated heat, and below the point where it often leans on backup heat. About 19 of those 185 nights reach 0°F or below, under a quarter of them, but even above 0°F a standard heat pump is running short.
A heat pump built to carry the ENERGY STAR Cold Climate label is tested to a different standard: at 5°F it has to deliver at least 1.75 units of heat for every unit of electricity it uses, and hold onto 70 percent of its 47°F capacity. A field test of prototype cold-climate heat pumps over two winters found backup heat covered only a small share of the load between 0°F and 35°F, and the unit ran on backup alone only rarely even at 0°F. The heat pump that makes sense in this county, if it's a heat pump at all, is one built for this cold, not the federal minimum.